.33 Hp

Up .33 Hp .5 Hp

 

RATING CONDITIONS FOR AIR CONDITIONING: 65ºF RETURN GAS * 0ºF SUBCOOLING * 95ºF AMBIENT (AIR OVER) * OPERATION AT 60HZ

Capacity (BTU/Hour) At The Indicated Evaporating Temperature

Condensing Temperature

-10

0

5

10

15

20

25

30

35

40

45

55

-23.3

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

12.8

ºF

ºC

80

26.7

1160

1660

1940

2260

2600

2980

3400

3860

4370

4930

5540

6960

90

32.2

980

1480

1760

2060

2371

2750

3140

3570

4040

4570

5140

6450

100

37.8

790

1290

1570

1860

2153

2510

2880

3280

3694

4200

4730

5940

110

43.3

1090

1360

1640

1924

2270

2610

2990

3400

3840

4330

5450

120

48.9

880

1140

1420

1710

2020

2340

2700

3080

3490

3940

4960

130

54.4

1190

1470

1770

2070

2400

2760

3140

3550

4480

140

60.0

1230

1510

1800

2110

2440

2790

3170

4020

Power in Watts At The Indicated Evaporating Temperature

Condensing Temperature

-10

0

5

10

15

20

25

30

35

40

45

55

-23.3

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

12.8

ºF

ºC

80

26.7

260

300

320

340

360

380

390

410

420

440

460

490

90

32.2

260

310

330

350

370

390

410

430

450

470

490

530

100

37.8

250

300

330

350

380

400

430

450

470

500

520

560

110

43.3

300

330

360

380

410

440

460

490

520

540

600

120

48.9

290

320

350

390

420

450

480

510

540

570

630

130

54.4

350

380

420

450

480

520

550

580

650

140

60.0

380

420

450

490

530

560

600

670

Current in Amperes At The Indicated Evaporating Temperature

Condensing

-10

0

5

10

15

20

25

30

35

40

45

55

Temperature

-23.3

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

12.8

ºF

ºC

80

26.7

2.5

2.6

2.6

2.7

2.7

2.8

2.8

2.9

2.9

2.9

3.0

3.1

90

32.2

2.5

2.6

2.6

2.7

2.7

2.8

2.9

2.9

3.0

3.0

3.1

3.2

100

37.8

2.5

2.6

2.6

2.7

2.8

2.8

2.9

3.0

3.0

3.1

3.2

3.3

110

43.3

2.6

2.6

2.7

2.8

2.8

2.9

3.0

3.1

3.2

3.3

3.4

120

48.9

2.6

2.6

2.7

2.8

2.9

2.9

3.0

3.1

3.2

3.3

3.5

130

54.4

2.7

2.8

2.9

3.0

3.1

3.2

3.3

3.4

3.6

140

60.0

2.8

2.8

2.9

3.1

3.2

3.3

3.4

3.7

Mass Flow in Pounds per Hour Power At The Indicated Evaporating Temperature

Condensing Temperature

-10

0

5

10

15

20

25

30

35

40

45

55

-23.3

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

12.8

ºF

ºC

80

26.7

15

21

25

29

34

39

44

50

57

70

70

90

90

32.2

13

20

24

28

32

37

43

49

56

60

70

90

100

37.8

11

18

22

26

31

36

41

47

54

60

70

90

110

43.3

16

20

25

29

34

39

45

52

60

70

90

120

48.9

14

18

23

27

32

37

43

50

57

64

82

130

54.4

20

25

30

35

41

47

54

62

79

140

60.0

22

27

33

39

45

52

59

76

All performance values are nominal and will be realized (+/- 5%) after a break-in period of a minimum of 72 hours.

Designs, and therefore performance, are subject to change without notice.

Figures in italics are restricted to a maximum return-gas temperature of 40ºF

Home ] Information ] Up ] [ .33 Hp ] .5 Hp ]

SCAN2.jpg (11933 bytes)Andover Protection Systems Inc.
63 Flushing Avenue, Bldg 5, Brooklyn, NY 11205 USA
Phone: 718-643-1110     FAX: 718-797-1120     E-mail: Click to E-mail
Click to E-mail with questions or comments about this web site.
Copyright© 1998-2006 Figment Design
Last modified: June 09, 2006