Home Information
.5 Hp

Up .33 Hp .5 Hp

 

RATING CONDITIONS FOR AIR CONDITIONING: 65ºF RETURN GAS * 0ºF SUBCOOLING * 95ºF AMBIENT (AIR OVER) * OPERATION AT 60HZ

Capacity (BTU/Hour) At The Indicated Evaporating Temperature

Condensing Temperature

-10

0

5

10

15

20

25

30

35

40

45

55

-23.3

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

12.8

ºF

ºC

80

26.7

1880

2540

2950

3410

3920

4490

5110

5790

6520

7320

8170

10060

90

32.2

1670

2270

2650

3090

3570

4110

4710

5360

6026

6840

7670

9510

100

37.8

1510

2040

2380

2780

3230

3740

4300

4920

5590

6330

7130

8900

110

43.3

1850

2150

2500

2910

3370

3890

4460

5100

5790

6550

8240

120

48.9

1700

1950

2250

2600

3010

3480

4010

4590

5230

5940

7540

130

54.4

2030

2320

2670

3080

3550

4070

4660

5310

6790

140

60.0

2080

2360

2700

3100

3550

4070

4660

6010

Power in Watts At The Indicated Evaporating Temperature

CondensingTemperature

-10

0

5

10

15

20

25

30

35

40

45

55

-23.3

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

12.8

ºF

ºC

80

26.7

360

410

440

470

500

530

560

590

610

640

670

710

90

32.2

360

410

440

480

510

540

580

610

650

680

710

780

100

37.8

360

420

450

480

520

560

600

640

680

720

760

840

110

43.3

420

460

490

530

570

610

660

700

750

800

890

120

48.9

430

460

500

540

580

630

680

720

780

830

940

130

54.4

500

540

590

640

690

740

800

860

980

140

60.0

540

590

640

690

750

810

870

1010

Current in Amperes At The Indicated Evaporating Temperature

Condensing Temperature

-10

0

5

10

15

20

25

30

35

40

45

55

-23.3

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

12.8

ºF

ºC

80

26.7

3.0

3.2

3.2

3.3

3.4

3.5

3.6

3.7

3.8

3.9

3.9

4.1

90

32.2

3.0

3.2

3.2

3.3

3.4

3.5

3.6

3.8

3.9

4.0

4.1

4.4

100

37.8

3.1

3.2

3.3

3.3

3.5

3.6

3.7

3.8

4.0

4.1

4.3

4.6

110

43.3

3.2

3.3

3.4

3.5

3.6

3.8

3.9

4.1

4.2

4.4

4.8

120

48.9

3.2

3.3

3.4

3.5

3.7

3.8

4.0

4.2

4.3

4.5

5.0

130

54.4

3.4

3.5

3.7

3.8

4.0

4.2

4.4

4.6

5.1

140

60.0

3.5

3.7

3.8

4.0

4.2

4.5

4.7

5.2

Mass Flow in Pounds per Hour Power At The Indicated Evaporating Temperature

Condensing Temperature

-10

0

5

10

15

20

25

30

35

40

45

55

-23.3

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

12.8

ºF

ºC

80

26.7

22

30

35

41

47

54

61

69

78

90

100

120

90

32.2

20

28

33

38

44

51

58

66

75

90

100

120

100

37.8

19

26

30

35

41

48

55

63

72

80

90

120

110

43.3

24

28

33

38

45

52

59

68

80

90

110

120

48.9

23

27

31

36

42

48

56

64

73

83

106

130

54.4

29

33

38

44

51

59

68

78

100

140

60.0

31

35

41

47

54

62

71

93

All performance values are nominal and will be realized (+/- 5%) after a break-in period of a minimum of 72 hours.

Designs, and therefore performance, are subject to change without notice.

Figures in italics are restricted to a maximum return-gas temperature of 40ºF

Home ] Information ] Up ] .33 Hp ] [ .5 Hp ]

SCAN2.jpg (11933 bytes)Andover Protection Systems Inc.
63 Flushing Avenue, Bldg 5, Brooklyn, NY 11205 USA
Phone: 718-643-1110     FAX: 718-797-1120     E-mail: Click to E-mail
Click to E-mail with questions or comments about this web site.
Copyright© 1998-2006 Figment Design
Last modified: June 09, 2006