RATING CONDITIONS FOR AIR CONDITIONING: 65ºF RETURN GAS * 0ºF SUBCOOLING * 95ºF AMBIENT (AIR OVER) * OPERATION AT 60HZ

Capacity (BTU/Hour) At The Indicated Evaporating Temperature

Condensing

0

5

10

15

20

25

30

35

45

55

Temperature

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

7.2

12.8

ºF

ºC

70

21.1

11170

13440

15980

18790

21900

25300

29020

33060

42160

52700

80

26.7

10360

12520

14940

17620

20580

23830

27380

31240

39940

50020

90

32.2

9570

11610

13880

16410

19200

22270

25630

29280

37540

47130

100

37.8

8820

10710

12820

15180

17780

20650

23790

27220

34980

44040

110

43.3

8130

9850

11780

13930

16320

18970

21870

25060

32290

40760

120

48.9

9040

10760

12690

14850

17250

19900

22810

29470

37310

130

54.4

9780

11480

13380

15520

17890

20510

26540

33720

140

60.0

10300

11930

13780

15850

18150

23520

29990

Power in Watts At The Indicated Evaporating Temperature

Condensing

0

5

10

15

20

25

30

35

45

55

Temperature

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

7.2

12.8

ºF

ºC

70

21.1

1260

1330

1400

1450

1500

1540

1580

1620

1680

1730

80

26.7

1390

1470

1550

1620

1680

1740

1790

1840

1920

2000

90

32.2

1500

1600

1690

1780

1850

1930

1990

2050

2160

2260

100

37.8

1590

1710

1820

1920

2010

2100

2180

2250

2390

2520

110

43.3

1660

1790

1920

2030

2140

2250

2340

2440

2610

2760

120

48.9

1850

1990

2120

2250

2370

2490

2600

2800

2990

130

54.4

2030

2180

2330

2470

2600

2730

2970

3190

140

60.0

2200

2370

2530

2680

2830

3110

3370

Current in Amperes At The Indicated Evaporating Temperature

Condensing

0

5

10

15

20

25

30

35

45

55

Temperature

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

7.2

12.8

ºF

ºC

70

21.1

4.7

4.8

4.9

5.0

5.1

5.2

5.3

5.3

5.5

5.6

80

26.7

4.9

5.1

5.2

5.4

5.5

5.6

5.7

5.8

6.0

6.2

90

32.2

5.1

5.3

5.5

5.7

5.8

6.0

6.1

6.3

6.5

6.8

100

37.8

5.3

5.5

5.7

5.9

6.1

6.3

6.5

6.7

7.0

7.4

110

43.3

5.3

5.6

5.9

6.2

6.4

6.7

6.9

7.1

7.5

7.9

120

48.9

5.7

6.1

6.4

6.7

6.9

7.2

7.5

8.0

8.5

130

54.4

6.1

6.5

6.9

7.2

7.5

7.8

8.4

9.1

140

60.0

6.6

7.0

7.4

7.8

8.2

8.9

9.6

Mass Flow in Pounds per Hour Power At The Indicated Evaporating Temperature

Condensing

0

5

10

15

20

25

30

35

45

55

Temperature

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

7.2

12.8

ºF

ºC

70

21.1

134

161

191

225

263

304

350

400

514

650

80

26.7

127

154

184

218

255

296

341

391

505

640

90

32.2

122

148

177

210

247

287

332

381

494

630

100

37.8

117

142

171

202

238

277

321

369

480

610

110

43.3

113

137

164

194

228

266

309

356

464

590

120

48.9

132

157

186

218

254

295

340

444

569

130

54.4

150

176

206

240

279

321

421

542

140

60.0

166

193

225

260

300

395

511

All performance values are nominal and will be realized (+/- 5%) after a break-in period of a minimum of 24 hours.

Designs, and therefore performance, are subject to change without notice.

Figures in italics are restricted to a maximum return-gas temperature of 40ºF

Home ] Information ] Up ] 1.5 hp ] 2 hp ] 2 hp CF ] 2.5 hp ] [ 2.5 hp CG&H ] 3 hp ] 4 hp ] 5 hp ]

SCAN2.jpg (11933 bytes)Andover Protection Systems Inc.
63 Flushing Avenue, Bldg 5, Brooklyn, NY 11205 USA
Phone: 718-643-1110     FAX: 718-797-1120     E-mail: Click to E-mail
Click to E-mail with questions or comments about this web site.
Copyright© 1998-2006 Figment Design
Last modified: June 09, 2006