Home Information
2 hp CF

Up 1.5 hp 2 hp 2 hp CF 2.5 hp 2.5 hp CG&H 3 hp 4 hp 5 hp

MODELS 0200-CF-*

RATING CONDITIONS FOR AIR CONDITIONING: 20ºF SUPERHEAT * 15ºF SUBCOOLING * 95ºF AMBIENT (AIR OVER) * OPERATION AT 60HZ

Capacity (BTU/Hour) At The Indicated Evaporating Temperature

Condensing

-10

-5

0

5

10

15

20

25

30

35

40

45

50

55

Temperature

-23.3

-20.6

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

7540

8917

10600

12355

14500

16750

19500

22200

25500

28650

32500

36400

40500

44900

90

32.2

6670

7980

9580

11209

13200

15270

17800

20320

23400

26325

29900

33500

37200

41200

100

37.8

5670

7011

8650

10158

12000

13890

16200

18585

21500

24245

27600

30800

34200

37800

110

43.3

4420

5883

7670

9079

10800

12555

14700

16905

19600

22210

25400

28400

31500

34700

120

48.9

6510

7986

9790

11415

13400

15425

17900

20330

23300

26200

29100

31900

130

54.4

8690

10225

12100

13990

16300

18595

21400

24100

26800

29500

140

60.0

7340

8942

10900

12655

14800

16915

19500

22100

24700

27300

150

65.6

Power in Watts At The Indicated Evaporating Temperature

Condensing

-10

-5

0

5

10

15

20

25

30

35

40

45

50

55

Temperature

-23.3

-20.6

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

1180

1234

1300

1354

1420

1461

1510

1533

1560

1560

1560

1540

1490

1430

90

32.2

1200

1268

1350

1413

1490

1544

1610

1655

1710

1728

1750

1750

1730

1690

100

37.8

1200

1286

1390

1462

1550

1618

1700

1763

1840

1881

1930

1950

1950

1930

110

43.3

1150

1272

1420

1506

1610

1691

1790

1862

1950

2009

2080

2120

2150

2150

120

48.9

1410

1518

1650

1745

1860

1950

2060

2137

2230

2290

2330

2350

130

54.4

1680

1788

1920

2024

2150

2245

2360

2440

2510

2540

140

60.0

1660

1800

1970

2087

2230

2343

2480

2590

2670

2730

150

65.6

Current in Amperes At The Indicated Evaporating Temperature

Condensing

-10

-5

0

5

10

15

20

25

30

35

40

45

50

55

Temperature

-23.3

-20.6

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

5.4

5.6

5.9

6.1

6.3

6.5

6.7

6.8

7.0

7.0

7.0

6.8

6.7

6.4

90

32.2

5.4

5.7

6.1

6.3

6.6

6.9

7.2

7.3

7.6

7.7

7.8

7.8

7.7

7.5

100

37.8

5.4

5.8

6.2

6.5

6.9

7.2

7.6

7.8

8.1

8.3

8.5

8.6

8.6

8.6

110

43.3

5.2

5.7

6.3

6.7

7.1

7.5

7.9

8.2

8.7

8.9

9.2

9.4

9.5

9.5

120

48.9

6.3

6.8

7.3

7.7

8.2

8.6

9.1

9.4

9.9

10.1

10.3

10.4

130

54.4

7.5

7.9

8.5

9.0

9.5

9.9

10.4

10.8

11.1

11.2

140

60.0

7.4

8.0

8.7

9.2

9.9

10.4

11.0

11.4

11.8

12.0

150

65.6

Mass Flow in Pounds per Hour Power At The Indicated Evaporating Temperature

Condensing

-10

-5

0

5

10

15

20

25

30

35

40

45

50

55

Temperature

-23.3

-20.6

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

97

114

134

155

181

208

240

272

311

347

392

436

482

532

90

32.2

89

106

126

146

171

197

228

259

296

331

374

416

460

505

100

37.8

79

96

118

137

161

186

216

246

282

316

358

398

439

482

110

43.3

64

85

110

129

153

176

205

234

269

302

343

382

421

460

120

48.9

98

118

144

167

194

222

257

289

329

367

405

442

130

54.4

134

157

185

212

245

277

316

354

392

427

140

60.0

120

145

175

202

234

266

304

342

379

415

150

65.6

Energy Efficiency Rating (EER) in BTU/Watt-Hr At The Indicated Evaporating Temperature

Condensing

-10

-5

0

5

10

15

20

25

30

35

40

45

50

55

Temperature

-23.3

-20.6

-17.8

-15.0

-12.2

-9.4

-6.7

-3.9

-1.1

1.7

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

6.4

7.1

8.1

9.1

10.2

11.4

12.9

14.4

16.3

18.3

20.8

23.6

27.1

31.3

90

32.2

5.5

6.2

7.1

7.9

8.9

9.8

11.0

12.2

13.7

15.2

17.1

19.1

21.5

24.3

100

37.8

4.7

5.4

6.2

6.9

7.7

8.5

9.5

10.5

11.7

12.9

14.3

15.8

17.6

19.6

110

43.3

3.8

4.6

5.4

6.0

6.8

7.5

8.3

9.1

10.0

11.0

12.2

13.4

14.7

16.1

120

48.9

4.6

5.2

5.9

6.5

7.2

7.9

8.7

9.5

10.5

11.4

12.5

13.6

130

54.4

5.2

5.7

6.3

6.9

7.6

8.3

9.1

9.9

10.7

11.6

140

60.0

4.4

4.9

5.5

6.0

6.6

7.2

7.9

8.6

9.3

10.0

150

65.6

All performance values are nominal and will be realized (+/- 5%) after a break-in period of a minimum of 24 hours.

Designs, and therefore performance, are subject to change without notice.

 

Home ] Information ] Up ] 1.5 hp ] 2 hp ] [ 2 hp CF ] 2.5 hp ] 2.5 hp CG&H ] 3 hp ] 4 hp ] 5 hp ]

SCAN2.jpg (11933 bytes)Andover Protection Systems Inc.
63 Flushing Avenue, Bldg 5, Brooklyn, NY 11205 USA
Phone: 718-643-1110     FAX: 718-797-1120     E-mail: Click to E-mail
Click to E-mail with questions or comments about this web site.
Copyright© 1998-2006 Figment Design
Last modified: June 09, 2006