MODELS 0500-CT-* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RATING CONDITIONS FOR AIR CONDITIONING: 65ºF RETURN GAS * 0ºF SUBCOOLING *
95ºF AMBIENT (AIR OVER) * OPERATION AT 60HZ |
|
|
|
|
|
|
|
|
|
|
|
|
Capacity (BTU/Hour) At The Indicated Evaporating Temperature |
|
|
|
|
|
|
|
|
|
|
|
|
Condensing |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
35 |
45 |
55 |
Temperature |
-17.8 |
-15.0 |
-12.2 |
-9.4 |
-6.7 |
-3.9 |
-1.1 |
1.7 |
7.2 |
12.8 |
|
|
|
|
|
|
|
|
|
|
|
|
ºF |
ºC |
|
|
|
|
|
|
|
|
|
|
70 |
21.1 |
30390 |
35210 |
40350 |
45880 |
51890 |
58450 |
65650 |
73540 |
91760 |
113730 |
80 |
26.7 |
27550 |
32300 |
37320 |
42670 |
48420 |
54670 |
61480 |
68930 |
86050 |
106660 |
90 |
32.2 |
24550 |
29270 |
34190 |
39370 |
44900 |
50850 |
57300 |
64320 |
80400 |
99710 |
100 |
37.8 |
21400 |
26120 |
30960 |
36000 |
41320 |
47000 |
53110 |
59740 |
74810 |
92860 |
110 |
43.3 |
18100 |
22830 |
27620 |
32540 |
37680 |
43120 |
48910 |
55160 |
69280 |
86110 |
120 |
48.9 |
|
19410 |
24170 |
29000 |
33980 |
39190 |
44700 |
50590 |
63810 |
79460 |
130 |
54.4 |
|
|
20610 |
25370 |
30220 |
35220 |
40470 |
46020 |
58380 |
72920 |
140 |
60.0 |
|
|
|
21660 |
26390 |
31220 |
36210 |
41460 |
53010 |
66470 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power in Watts At The Indicated Evaporating Temperature |
|
|
|
|
|
|
|
|
|
|
|
|
Condensing |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
35 |
45 |
55 |
Temperature |
-17.8 |
-15.0 |
-12.2 |
-9.4 |
-6.7 |
-3.9 |
-1.1 |
1.7 |
7.2 |
12.8 |
|
|
|
|
|
|
|
|
|
|
|
|
ºF |
ºC |
|
|
|
|
|
|
|
|
|
|
70 |
21.1 |
3250 |
3380 |
3480 |
3550 |
3600 |
3610 |
3600 |
3550 |
3360 |
3050 |
80 |
26.7 |
3340 |
3520 |
3680 |
3810 |
3910 |
3980 |
4020 |
4040 |
3970 |
3780 |
90 |
32.2 |
3380 |
3620 |
3840 |
4020 |
4180 |
4310 |
4410 |
4480 |
4530 |
4460 |
100 |
37.8 |
3390 |
3680 |
3950 |
4190 |
4400 |
4590 |
4740 |
4870 |
5040 |
5100 |
110 |
43.3 |
3360 |
3700 |
4020 |
4320 |
4580 |
4820 |
5040 |
5220 |
5510 |
5680 |
120 |
48.9 |
|
3680 |
4050 |
4400 |
4720 |
5010 |
5280 |
5530 |
5930 |
6220 |
130 |
54.4 |
|
|
4040 |
4440 |
4810 |
5160 |
5480 |
5780 |
6300 |
6710 |
140 |
60.0 |
|
|
|
4430 |
4860 |
5260 |
5640 |
5990 |
6620 |
7140 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Current in Amperes At The Indicated Evaporating Temperature |
|
|
|
|
|
|
|
|
|
|
|
|
Condensing |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
35 |
45 |
55 |
Temperature |
-17.8 |
-15.0 |
-12.2 |
-9.4 |
-6.7 |
-3.9 |
-1.1 |
1.7 |
7.2 |
12.8 |
|
|
|
|
|
|
|
|
|
|
|
|
ºF |
ºC |
|
|
|
|
|
|
|
|
|
|
70 |
21.1 |
14.9 |
15.5 |
15.9 |
16.2 |
16.4 |
16.4 |
16.3 |
16.1 |
15.3 |
14.0 |
80 |
26.7 |
15.3 |
16.1 |
16.7 |
17.3 |
17.7 |
18.0 |
18.2 |
18.2 |
17.9 |
17.1 |
90 |
32.2 |
15.5 |
16.5 |
17.4 |
18.2 |
18.9 |
19.4 |
19.8 |
20.1 |
20.4 |
20.1 |
100 |
37.8 |
15.5 |
16.7 |
17.9 |
18.9 |
19.9 |
20.7 |
21.3 |
21.9 |
22.6 |
22.9 |
110 |
43.3 |
15.3 |
16.8 |
18.2 |
19.5 |
20.6 |
21.7 |
22.6 |
23.4 |
24.7 |
25.5 |
120 |
48.9 |
|
16.6 |
18.3 |
19.8 |
21.2 |
22.5 |
23.7 |
24.7 |
26.5 |
27.8 |
130 |
54.4 |
|
|
18.1 |
19.9 |
21.6 |
23.1 |
24.5 |
25.8 |
28.1 |
30.0 |
140 |
60.0 |
|
|
|
19.8 |
21.7 |
23.4 |
25.1 |
26.7 |
29.5 |
31.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Mass Flow in Pounds per Hour Power At The Indicated Evaporating Temperature |
|
|
|
|
|
|
|
|
|
|
|
|
Condensing |
0 |
5 |
10 |
15 |
20 |
25 |
30 |
35 |
45 |
55 |
Temperature |
-17.8 |
-15.0 |
-12.2 |
-9.4 |
-6.7 |
-3.9 |
-1.1 |
1.7 |
7.2 |
12.8 |
|
|
|
|
|
|
|
|
|
|
|
|
ºF |
ºC |
|
|
|
|
|
|
|
|
|
|
70 |
21.1 |
361 |
419 |
481 |
547 |
620 |
700 |
789 |
888 |
1119 |
1400 |
80 |
26.7 |
338 |
398 |
460 |
527 |
600 |
679 |
766 |
863 |
1089 |
1370 |
90 |
32.2 |
313 |
374 |
437 |
505 |
577 |
656 |
742 |
837 |
1058 |
1330 |
100 |
37.8 |
284 |
347 |
412 |
480 |
553 |
632 |
717 |
811 |
1027 |
1290 |
110 |
43.3 |
253 |
317 |
384 |
453 |
526 |
605 |
690 |
782 |
995 |
1250 |
120 |
48.9 |
|
285 |
353 |
424 |
498 |
576 |
661 |
752 |
962 |
1213 |
130 |
54.4 |
|
|
319 |
391 |
466 |
545 |
629 |
720 |
927 |
1174 |
140 |
60.0 |
|
|
|
355 |
431 |
511 |
596 |
686 |
890 |
1133 |
|
|
|
|
|
|
|
|
|
|
|
|
All performance values are nominal and will be realized (+/- 5%) after a
break-in period of a minimum of 24 hours. |
Designs, and therefore performance, are subject to change without notice. |
Figures in italics are restricted to a maximum return-gas temperature of
40ºF |
|
|
|
|
|
|
|
|
|
|
|
|