Home Information
7.5 hp

Up 7.5 hp 10 hp 12 hp

MODELS 0750-BA-*

MODELS 0750-BB-*

RATING CONDITIONS FOR AIR CONDITIONING: 20ºF SUPERHEAT * 15ºF SUBCOOLING * 95ºF AMBIENT (AIR OVER) * OPERATION AT 60HZ

Capacity (BTU/Hour) At The Indicated Evaporating Temperature

Condensing

-10

0

10

20

30

40

45

50

55

Temperature

-23.3

-17.8

-12.2

-6.7

-1.1

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

29300

43000

58700

76900

98100

122900

136900

151900

168200

90

32.2

24600

37900

52900

70300

90600

114300

127700

142200

157800

100

37.8

19900

32600

46900

63500

82800

105500

118300

132100

147000

110

43.3

27300

40900

56600

75000

96600

108700

121900

136100

120

48.9

35200

50000

67300

87700

99200

111700

125200

130

54.4

29800

43600

59900

79100

89900

101700

114500

140

60.0

37800

52900

70800

81000

92100

104200

150

65.6

32600

46500

63200

72700

83000

94300

Power in Watts At The Indicated Evaporating Temperature

Condensing

-10

0

10

20

30

40

45

50

55

Temperature

-23.3

-17.8

-12.2

-6.7

-1.1

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

3990

4680

5210

5600

5860

6020

6060

6090

6090

90

32.2

3870

4710

5390

5920

6340

6650

6770

6880

6970

100

37.8

3690

4660

5480

6160

6720

7190

7390

7570

7740

110

43.3

4550

5500

6320

7030

7640

7910

8180

8420

120

48.9

5460

6410

7260

8010

8360

8690

9010

130

54.4

5360

6450

7430

8320

8740

9140

9530

140

60.0

6430

7540

8570

9050

9530

9990

150

65.6

6380

7610

8770

9320

9860

10390

Current in Amperes At The Indicated Evaporating Temperature

Condensing

-10

0

10

20

30

40

45

50

55

Temperature

-23.3

-17.8

-12.2

-6.7

-1.1

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

16.2

17.4

18.4

19.2

19.8

20.1

20.2

20.2

20.1

90

32.2

16.0

17.5

18.7

19.8

20.7

21.4

21.7

21.9

22.1

100

37.8

15.7

17.4

18.9

20.3

21.6

22.6

23.1

23.5

23.8

110

43.3

17.2

19.0

20.7

22.2

23.7

24.3

24.9

25.4

120

48.9

18.9

20.9

22.8

24.5

25.4

26.2

26.9

130

54.4

18.7

21.0

23.2

25.3

26.3

27.3

28.3

140

60.0

21.0

23.5

26.0

27.2

28.3

29.5

150

65.6

20.8

23.7

26.5

27.9

29.3

30.6

Mass Flow in Pounds per Hour Power At The Indicated Evaporating Temperature

Condensing

-10

0

10

20

30

40

45

50

55

Temperature

-23.3

-17.8

-12.2

-6.7

-1.1

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

376

546

734

947

1192

1477

1637

1810

2000

90

32.2

328

498

686

898

1143

1427

1586

1758

1940

100

37.8

277

446

632

843

1086

1369

1527

1697

1880

110

43.3

391

575

784

1025

1305

1461

1630

1810

120

48.9

517

723

961

1237

1392

1559

1740

130

54.4

461

663

896

1168

1321

1486

1660

140

60.0

605

833

1100

1250

1412

1588

150

65.6

551

774

1035

1182

1341

1513

Energy Efficiency Rating (EER) in BTU/Watt-Hr At The Indicated Evaporating Temperature

Condensing

-10

0

10

20

30

40

45

50

55

Temperature

-23.3

-17.8

-12.2

-6.7

-1.1

4.4

7.2

10.0

12.8

ºF

ºC

80

26.7

7.3

9.2

11.3

13.7

16.7

20.4

22.6

24.9

27.6

90

32.2

6.4

8.0

9.8

11.9

14.3

17.2

18.9

20.7

22.6

100

37.8

5.4

7.0

8.6

10.3

12.3

14.7

16.0

17.5

19.0

110

43.3

6.0

7.4

9.0

10.7

12.6

13.7

14.9

16.2

120

48.9

6.4

7.8

9.3

10.9

11.9

12.9

13.9

130

54.4

5.6

6.8

8.1

9.5

10.3

11.1

12.0

140

60.0

5.9

7.0

8.3

9.0

9.7

10.4

150

65.6

5.1

6.1

7.2

7.8

8.4

9.1

All performance values are nominal and will be realized (+/- 5%) after a break-in period of a minimum of 24 hours.

Designs, and therefore performance, are subject to change without notice.

Home ] Information ] Up ] [ 7.5 hp ] 10 hp ] 12 hp ]

SCAN2.jpg (11933 bytes)Andover Protection Systems Inc.
63 Flushing Avenue, Bldg 5, Brooklyn, NY 11205 USA
Phone: 718-643-1110     FAX: 718-797-1120     E-mail: Click to E-mail
Click to E-mail with questions or comments about this web site.
Copyright© 1998-2006 Figment Design
Last modified: June 09, 2006